F0 Error Code Gree AC Troubleshooting | U-Match Series

F0 Error Code Gree AC Troubleshooting | U-Match Series

Are you suffering from a F0 Error in your Gree Air Conditioner? Let me tell you F0 Error meaning is different every time according to the types of Gree AC Units. In this post, we going to talk about the F0 error gree inverter ac U-Match Series.

F0 Error in Gree Mini Split AC

F0 Error Gree AC U-Match Series

If you have a concealed or duct type air conditioner, the F0 error will stand for Ambient Temperature Sensor Problem. If the indoor ambient temperature sensor is detected of open circuit or short circuit for 5s successively, indoor ambient temperature sensor malfunction will be reported.
The unit can automatically resume operation after the malfunction disappears. Sometimes indoor ambient temperature sensor malfunction occurs in fan mode. Only the error code is displayed but the indoor unit can work normally.

Causes of Gree AC F0 Error U-Match Series

  1. The Ambient Temperature Sensor is not connected to the port properly.
  2. The sensor is weak, burned, broken, or short-circuited, so an F0 error appears.
  3. Indoor Main PCB Board Faulty.

 

 

F0 Error Code Troubleshooting Guide

  • Check if the indoor ambient temperature sensor on the mainboard is inserted into the needle stand correctly. Correctly insert the temperature sensor on the needle stand.
  • Disconnect the temperature sensor and measure for 20k ohms if its resistance is normal. If the resistance value is low change it.
  • Change the indoor Main PCB Board.

 

See the Flow Chart-

F0 Error Code Gree AC Troubleshooting | U-Match Series

 

 

Read more-

Gree AC All Error Codes | U-Match Series

How to Fix E6 Gree AC Error Code

How to Fix E8 Error Code Gree Inverter Air Conditioner

E9 Error Code Gree Inverter Air Conditioner Troubleshooting

Scroll to Top